Compute initial symmetrical short-circuit current I"k, peak current ip, breaking current I_b, and steady-state I_k per IEC 60909-0:2016 §4. Supports three-phase, single-line-to-ground, line-to-line, and double-line-to-ground faults. Used for breaker selection, transformer sizing, and protection relay settings.
| Parameter | Value |
|---|---|
| Voltage factor c | 1.1 |
| I"k — Initial symmetrical SC current (kA) | 8.585 kA |
| ip — Peak short-circuit current (kA) | 21.751 kA |
| id.c. — DC component at contact parting (kA) | 2.702 kA |
| Ib — Symmetrical breaking current (kA) | 8.585 kA |
| Ik — Steady-state SC current (kA) | 8.585 kA |
| κ — Peak factor | 1.7916 |
| X/R at fault bus | 12.545 |
| Fault type multiplier | 1 |
| Z_k total (Ω) | 1.4796 Ω |
| Network contribution (kA) | 8.585 kA |
| Breaking duty Ib (kA) | — kA |
| Breaking duty (%) | —% |
| Peak duty ip (kA) | — kA |
| Peak limit 2.5× (kA) | — kA |
| Overall | PASS |
| Element | R (Ω) | X (Ω) |
|---|---|---|
| Network | 0.0876 | 0.8756 |
| Transformer | 0.03 | 0.5992 |
| Total Zk | 0.1176 | 1.4749 |