Free Tool · IEEE 1584-2018 + DC Paukert · 3 Scenarios · Electrical

Arc Flash Study

Multi-bus, 3-scenario arc flash hazard study per IEEE 1584-2018 (AC systems) and DC Paukert method (PV solar DC only). Enter fault current from your short-circuit study, get per-bus incident energy, PPE category, arc flash boundary, and PDF-ready labels.

Short-Circuit Study (IEC 60909) →
Arc Flash Study (this page) →
Earthing / Grounding Study
Full Study · Multi-Bus · 3 Scenarios Quick Calc · Single-Point · IEEE 1584-2018
Study Inputs — Buses Auto-fill from voltage tier
Scenario 1 — Max (All Sources, Tie Closed)
Scenario 2 — Min (Min Utility, No Other Sources)
Scenario 3 — Typical (Intermediate)
Standards & References
IEEE 1584-2018
Guide for Performing Arc-Flash Hazard Calculations — 2018 revision with per-configuration regression equations (VCB, VCBB, HCB, VOA, HOA). Replaced 2002 single-equation model.
NFPA 70E-2021
Standard for Electrical Safety in the Workplace. PPE categories per Table 130.7(C)(15)(c): Cat 1 ≤4, Cat 2 ≤8, Cat 3 ≤25, Cat 4 ≤40 cal/cm².
OSHA Appendix E
OSHA 1910.333(a)(1) — General requirements for electrical protective equipment. Appendix E references IEEE 1584 for arc flash energy calculation methodology.
DC Paukert Method
Applies ONLY to PV solar array DC sources. E = 0.01 × I_sc × t × K (K=0.79 open air, K=0.90 confined). Not valid for AC systems.

Frequently Asked Questions

What are the three scenarios and why do I need all three?
Maximum fault (Scenario 1) assumes all sources are online and tie breakers are closed, giving the highest bolted fault current. This drives the incident energy upper bound and determines PPE requirements. Minimum fault (Scenario 2) assumes only the utility is online at minimum contribution and no other sources are active — this may result in longer clearing times and potentially higher incident energy despite lower fault current. Typical (Scenario 3) represents the normal operating configuration with intermediate source contributions. All three are required because NFPA 70E and IEEE 1584 both require the study to bound the hazard range, not just report a single point estimate.
When does the 2-second rule apply and when does it not?
The 2-second rule (IEEE 1584 §4.11) allows assuming the arc self-extinguishes within 2 seconds — reducing incident energy. It applies to freely burning arcs in air. It does NOT apply in confined spaces such as inside a Power Conversion System (PCS) enclosure, where arc cooling is limited and the arc may persist beyond 2 seconds regardless of protective device timing.
Can I use the maximum scenario result as a blanket label for all equipment?
No. Individual equipment labels are required per NFPA 70E. Each bus, switchgear compartment, or MCC section should have its own label reflecting the actual calculated incident energy for that location. Exception: PV Load Break Disconnectors (LBDs) and combiner boxes on the DC side may use a worst-case blanket label because their incident energy is relatively uniform across the array and individual labeling may be impractical at scale.
Our system includes both AC and DC (PV/BESS) sources — how do I handle both?
Use IEEE 1584-2018 for all AC sources and system configurations. Use the DC Paukert method exclusively for the PV array DC side — it is not valid for AC. The DC arc flash hazard from PV modules and combiner boxes must be assessed separately, and all DC sources must be included in the LOTO procedure referenced on high-energy (>40 cal/cm²) labels. The two hazard domains are independent and cannot be combined into a single incident energy value.
Equipment is rated >15 kV — what additional steps are required?
IEEE 1584-2018 is validated for voltages up to 15 kV. For equipment above 15 kV, the standard notes that ARCPRO™ software or the ETAP ArcFault Module should be used for final study determination. These tools use the IEEE 1584-2018 framework extended with additional electrode configuration data and empirical validation for higher voltages. FrameAI can provide preliminary estimates for >15 kV systems, but a qualified engineer should validate with industry-standard software before finalizing labels.
What information do I need from a short-circuit study before running this tool?
You need the bolted three-phase fault current (Ibf) at each bus for your three scenarios. Maximum scenario: Ibf_max from the maximum fault study with all sources online. Minimum scenario: Ibf_min from the minimum fault study with only utility contribution. Typical scenario: Ibf_typ from your normal operating configuration. You also need the upstream protective device clearing time at each bus — read from the time-current characteristic (TCC) curve of the upstream breaker. If you do not have a short-circuit study yet, use FrameAI's free IEC 60909 short-circuit calculator.
How do I generate actual arc flash labels for my equipment?
After running the study, enter your equipment name and study date in the Labels section and click "Send Labels." The label set (JSON) is emailed to you and contains: Danger/Warning header per ANSI Z535, Arc Flash and Shock Hazard list, incident energy + working distance, arc flash boundary, nominal voltage, equipment name, study date, and the note "weather + UV resistant, minimum 5-year life." Labels should be printed on durable material and affixed to each piece of equipment per NFPA 70E §130.5.