FAQ
Why 15% safety factor?
Solar EPC specs require a 15% grid strength growth factor applied to utility MVA from the interconnection study. The grid is assumed 15% stronger (lower Z), increasing fault currents conservatively. Justify in project report.
How does inverter contribution work?
Inverters act as current-limited sources โ 1.0โ1.1ร rated current per IEEE 1547. Unlike rotating machines, they have very low X/R and minimal DC offset. Add the contribution algebraically to grid + motor contributions.
When does SLG govern over 3-phase?
SLG can exceed 3P in effectively grounded systems with low zero-sequence impedance relative to positive sequence (untransposed lines, certain transformer connections). Run both and select higher for device rating.
What clearing time should I use?
30 cycles (0.5s) for backup clearing per solar EPC spec. Primary clearing is typically 5โ8 cycles. Use backup time for interrupting duty; primary for relay coordination.
How is transformer impedance tolerance handled?
Per IEEE C57.12.00 ยง9.2: ยฑ10% tolerance. Use Z_max = 1.1ร rated for worst-case device duty, Z_min = 0.9ร for voltage sag studies.
How does this compare to IEC 60909?
IEC 60909 uses a c-factor (1.1 for max) and a different ฮบ table. IEEE C37.010 uses the E/X method with actual X/R. Both are valid; IEEE is standard for US solar. See /tools/short-circuit-iec for IEC.