Pro/Studio Tool · IEC 60947-2 / IEC 60364-4-43

Protective Device Coordination

MCCB/MCB <strong>selectivity</strong>, short-circuit <strong>I<sub>k</sub></strong> at each protection level, <strong>breaking capacity</strong> verification, <strong>I²t thermal discrimination</strong>, and <strong>cable thermal withstand</strong> per IEC 60364-5-54. Upstream/downstream coordination with backup protection check.

Include Backup Protection Check
I_k upstream (kA)
kA
I_k downstream (kA)
kA
Peak current I_p (kA)
kA
Selectivity verdict
Selectivity Current-based Time-based I_rm up I_rm down Ratio
Breaking Capacity I_cu (kA) I_k (kA) Result
Thermal Discrimination I²t upstream (A²s) I²t downstream (A²s) Result
Cable I²t fault (A²s) k²S² (A²s) k Result

Recommendations

    Export calculation report

    Enter your email to receive a formatted IEC 60947-2 protective device coordination report.

    Frequently Asked Questions

    Total selectivity (discrimination) means the upstream device will clear a downstream fault without the downstream device tripping. Per IEC 60947-2, this requires Irm_upstream > 1.5 × Irm_downstream (current-based) and sufficient time delay in the upstream device so that the downstream clears first on any fault level within its breaking capacity.
    Ik_down = c·U_n / (√3·Z_total) per IEC 60909, where Z_total = Z_source + Z_cable. Z_source is derived from the provided supply Ik at the origin. Cable impedance Z_cable = √(R²+X²) using the conductor material resistivity and reactance per unit length. For a 400V / 10kA supply with 50m of 10mm² copper, Ik at the load terminals is approximately 2–3 kA.
    Backup protection is required when the downstream device has a breaking capacity (Icu) less than the short-circuit current at its installation point (Ik_downstream). In this case the upstream device must be able to clear the downstream fault if the downstream device fails to interrupt. IEC 60364-4-43 §434.3 requires coordination so that the upstream device provides backup when the downstream is inadequate.
    IEC 60947-2 requires that the energy let-through of the upstream device (I²t_up) exceeds that of the downstream device (I²t_down) at the downstream trip current. This ensures the upstream device trips last, protecting the downstream coordination zone. Calculated as I²t = I_r² × t_trip for each device. The upstream must have I²t_up > I²t_down for discriminative coordination.
    Per IEC 60364-5-54 §543, the cable must withstand the thermal effects of the short-circuit current without damage. The criterion is I²t_fault ≤ k²·S², where k is a factor depending on conductor material and insulation (k=143 for Cu/PVC, k=115 for Al/PVC, k=76 for Cu/XLPE). If I²t exceeds k²S², the cable cross-section must be increased or a current-limiting device must be installed upstream.
    400V system, Ik=10 kA at origin, upstream 250A MCCB Type C Icu=25kA (tripping time 50ms), downstream 63A MCB Type C Icu=10kA (tripping time 20ms), Cu 10mm² 50m cable. Expected result: Ik downstream ≈ 2.07 kA, both breaking capacity PASS, total selectivity ( Irm upstream=1250A > 1.5×315A=472A ), I²t upstream ≈ 78,750 A²s >> I²t downstream ≈ 1,489 A²s → PASS, cable thermal PASS.