Poste IEC 62271-200

Sélection Appareillage MT (IEC 62271)

Sélection appareillage blindé AC — Ur 3,6–40,5 kV. Code panneau, niveaux d isolation, déclassement altitude/température, classification AIC, configuration baie.

IEC 62271-200 IEC 62271-1 IEC 62271-100 IEC 60909 IEC 60664-1 IEC 60865-1
Code Panneau
Insulation Level (Table 1)
ParameterValue
Up (impulse kV)
Ud (power-freq kV)
Ur (kV)
Derating Factors
Facteur Ka altitude
K_temp
Courant déclassé Ir (A)
κ factor
Ip auto (kA)
K_temp is indicative — verify with manufacturer curves
Internal Arc Energy
MJ equivalent
IAC Classification
cos(φ_arc)
Bay Configuration
Insulation Technology
Scores
Comparaison Appareillage
Standards Compliance
Export
Panel Type Code Construction

Code follows IEC 62271-200 §3 nomenclature.

[type] [Ur] / [Ir] / [Ik-tk] [/ LSC] [- partition] [/ IAC]
AIS 12kV / 1250A / 25kA-1s / LSC2B-PM / IAC AFLR 25kA 1s
Insulation Levels (Table 1)

Up = rated impulse, Ud = power-frequency withstand. Ka correction for altitude.

Ud_corrected = Ud / Ka (H > 1000 m)
Altitude & Temperature Derating

Ka = e^((H-1000)/8150). K_temp ≈ 1 - 0.012 × (T_max - 40°C).

Ir_final = Ir × Ka × K_temp
Internal Arc Classification

Ek = √3 × Ur × Ik × t × cos(φ_arc). AFLR = all four faces arc-resistant.

Ek = √3 · Ur · Ik · t · cos(φ_arc) (cos≈0.7 per IEC 60865-1)
Bay Configuration Selection

LSC1 → single busbar. LSC2A/2B + high → double busbar. LSC2B + standard → single with bypass.