IEC 60909-0:2016 · 国内規格 · 電気

IEC 60909 短絡電流

国内規格選択、K_TおよびK_G修正係数、発電機寄与を含む完全なIEC 60909-0:2016解析。

国内規格 / 標準:
IEC 60909 VDE 0102 (DE) BS 7639 (UK) GB/T 15544 (CN) JIS C 4620 (JP) IS 13234 (IN)
c_max = 1.10 (LV) / 1.10 (HV)
System One-Line Diagram
SUPPLY Un · Z_Q Z_src R + jX TR K_T= CABLE r·l x·l FAULT BUS G K_G F FAULT CURRENTS · IEC 60909 I"k = ip = κ = Ib = Ith = μ = R/X = Z_k = NA = IEC c = Fault= 3ph K_T =
R/X:
κ:
Z_k: Ω
NA: IEC
c: 1.10
System Parameters
kV
線間公称電圧
Hz
s
熱等価電流計算用(標準0.5 s)
電源インピーダンス
Ω
Ω
PCC点での系統インピーダンス
変圧器(任意)
MVA
%
kW
Pk=0の場合R/X≈0.05を使用
ケーブル(任意)
Ω/km
Ω/km
km
同期発電機(任意)
MVA
pu
典型:0.12–0.25 pu
R/X
典型:0.05–0.15
Select national annex, enter parameters, and click Calculate.
Includes K_T (transformer) and K_G (generator) impedance correction factors.
規格と国内附属書
IEC 60909-0:2016
International standard. c_max = 1.10 (LV + HV). Defines equivalent voltage source method, κ factor, m/n factors, K_T and K_G correction.
VDE 0102 (Germany)
German national implementation of IEC 60909-0. c_max = 1.05 for LV networks (≤ 1 kV), 4.5% lower maximum fault currents. Standard for switchgear selection in Germany and Austria.
BS 7639 (UK)
British standard for short-circuit calculation, harmonised with IEC 60909-0. Same c-factor table as IEC. Used alongside Engineering Recommendation G74 for UK distribution networks.
GB/T 15544 (China)
Chinese national standard harmonised with IEC 60909. Symmetrical component method, same c-factors. Required for grid fault level studies in China. Supplemented by DL/T 5222 for power system planning.
JIS C 4620 (Japan)
Japanese switchgear standard referencing IEC 60909 method for rated short-circuit withstand current. 50/60 Hz mixed grid. Used with IEC 62271-200 for LV/MV switchgear selection.
IS 13234 (India)
Indian standard for three-phase fault level calculation based on IEC 60909 method. 50 Hz grid. Used with IS 13118 for switchgear selection across HV/MV/LV levels.

よくある質問

/tools/short-circuit-iecとの違いは?
このフラッグシップ版は国内規格選択(VDE 0102 LV cmax=1.05)、K_TおよびK_G修正係数、μ係数付き同期発電機寄与を追加しています。
K_Tとは何ですか?
K_T=0.95×cmax/(1+0.6×x_T)(IEC 60909式12a)。タップ切換え位置と事故前電圧を補正します。
K_Gとは何ですか?
K_GはIEC 60909 §3.6.1式(18)に基づき、発電機の運転電圧と負荷角を補正します。
μ係数とは何ですか?
μは発電機近傍の遮断電流Ibを補正します。発電機遠方の場合はμ=1(Ib=I"k)です。
VDE 0102とは何ですか?
VDE 0102はIEC 60909-0のドイツ実装です。主な違い:低圧cmax=1.05(IEC=1.10)により、低圧系統の最大短絡電流が4.5%低くなります。
ANSI/IEEE C37との比較は?
IEC 60909は等価電圧源法(故障点でc×Un/√3)を使用し、潮流事前計算が不要です。ANSI/IEEE C37はThevenin等価電圧を使用します。IEC 60909は欧州・中東・アジア・アフリカで標準的な方法です。