高調波歪み限度値

IEEE 519-2014 · 表1〜4 · THD-V · TDD-I · 次数別適合

Presets
PCC パラメータ
高調波電流 Ih(IL比 %)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
高調波電圧 Vh(V₁比 %)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
Run the calculator to see THD-V, TDD-I, and per-harmonic compliance.
計算手法

THD-V = √(Σ Vh²) / V₁ × 100   [IEEE 519-2014 Table 1]

TDD-I = √(Σ Ih²) / IL × 100   [IEEE 519-2014 §10.2]

Isc/IL ratio selects the current distortion limit row from Table 2 (≤69 kV), Table 3 (69–161 kV), or Table 4 (>161 kV).

Even harmonics are limited to 25% of odd harmonic limits in the same group (§5.1).

Harmonic groups: h<11 · 11≤h<17 · 17≤h<23 · 23≤h<35 · h≥35

Voltage distortion limits (Table 1): LV ≤1 kV → THD 8%, indiv 5%; MV ≤69 kV → THD 5%, indiv 3%; HV 69–161 kV → THD 2.5%, indiv 1.5%; EHV >161 kV → THD 1.5%, indiv 1%.

FAQ
IEEE 519-2014とは?
IEEE 519-2014は電力系統における高調波制御のIEEE推奨慣行です。需要家と電力会社の接続点(PCC)における電圧・電流の高調波歪み限度を規定します。
TDDとTHDの違いは?
THDは基本波に対する高調波の割合。TDDは高調波電流を最大需要電流ILで正規化したもので、軽負荷時に誤った適合判定を防ぎます。IEEE 519は電流限度にTDDを使用します。
Isc/ILが限度値に与える影響は?
Isc/IL比が高いほど系統インピーダンスが低く(剛性)、より多くの高調波電流を吸収できます。IEEE 519は剛性系統に対してより高い限度値を認めます。
偶数次規則とは?
§5.1に基づき、偶数次高調波(2次、4次、6次…)は同グループの奇数次限度値の25%に制限されます。
どの電圧クラスを選択すればよいですか?
PCC線間電圧で判定:LV ≤ 1 kV(THD 8%);MV ≤ 69 kV(THD 5%);HV 69–161 kV(THD 2.5%);EHV > 161 kV(THD 1.5%)。
代表的な高調波発生源は?
6パルスVFDは5次・7次・11次・13次を発生。12パルスドライブは5次/7次を抑制。UPS/サーバーは3次・5次・7次を発生。VSCインバータ(太陽光/BESS)は広帯域スペクトルを発生。