Limiti Distorsione Armonica

IEEE 519-2014 · Tabelle 1–4 · THD-V · TDD-I · Conformità per Armonico

Presets
Parametri PCC
Correnti armoniche Ih (% di IL)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
Tensioni armoniche Vh (% di V₁)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
Run the calculator to see THD-V, TDD-I, and per-harmonic compliance.
Metodologia

THD-V = √(Σ Vh²) / V₁ × 100   [IEEE 519-2014 Table 1]

TDD-I = √(Σ Ih²) / IL × 100   [IEEE 519-2014 §10.2]

Isc/IL ratio selects the current distortion limit row from Table 2 (≤69 kV), Table 3 (69–161 kV), or Table 4 (>161 kV).

Even harmonics are limited to 25% of odd harmonic limits in the same group (§5.1).

Harmonic groups: h<11 · 11≤h<17 · 17≤h<23 · 23≤h<35 · h≥35

Voltage distortion limits (Table 1): LV ≤1 kV → THD 8%, indiv 5%; MV ≤69 kV → THD 5%, indiv 3%; HV 69–161 kV → THD 2.5%, indiv 1.5%; EHV >161 kV → THD 1.5%, indiv 1%.

FAQ
Cos'è IEEE 519-2014?
IEEE 519-2014 fissa i limiti di distorsione armonica in tensione e corrente al punto di accoppiamento comune (PCC) tra cliente e rete.
TDD vs THD?
THD esprime le armoniche rispetto al fondamentale. TDD esprime le armoniche di corrente rispetto alla corrente di carico massima IL. IEEE 519 usa TDD per i limiti di corrente.
Come influisce Isc/IL sui limiti?
Un rapporto Isc/IL maggiore indica una rete più rigida che può assorbire più armoniche. IEEE 519 concede limiti più alti per reti rigide.
Qual è la regola delle armoniche pari?
Secondo §5.1, le armoniche pari sono limitate al 25% dei limiti delle armoniche dispari corrispondenti.
Quale classe di tensione si applica?
BT ≤ 1 kV (THD 8%); MT ≤ 69 kV (THD 5%); AT 69–161 kV (THD 2,5%); EAT > 161 kV (THD 1,5%).
Quali sono le sorgenti armoniche tipiche?
Inverter 6 impulsi generano 5°, 7°, 11°, 13° armonica. Azionamenti 12 impulsi sopprimono 5°/7°. UPS/server generano 3°, 5°, 7°. Inverter VSC producono uno spettro ampio.