Límites de Distorsión Armónica

IEEE 519-2014 · Tablas 1–4 · THD-V · TDD-I · Cumplimiento por Armónico

Presets
Parámetros del PCC
Corrientes armónicas Ih (% de IL)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
Tensiones armónicas Vh (% de V₁)
h=2
h=3
h=4
h=5
h=6
h=7
h=8
h=9
h=10
h=11
h=13
h=17
h=19
h=23
h=25
h=35
h=47
h=49
Run the calculator to see THD-V, TDD-I, and per-harmonic compliance.
Metodología

THD-V = √(Σ Vh²) / V₁ × 100   [IEEE 519-2014 Table 1]

TDD-I = √(Σ Ih²) / IL × 100   [IEEE 519-2014 §10.2]

Isc/IL ratio selects the current distortion limit row from Table 2 (≤69 kV), Table 3 (69–161 kV), or Table 4 (>161 kV).

Even harmonics are limited to 25% of odd harmonic limits in the same group (§5.1).

Harmonic groups: h<11 · 11≤h<17 · 17≤h<23 · 23≤h<35 · h≥35

Voltage distortion limits (Table 1): LV ≤1 kV → THD 8%, indiv 5%; MV ≤69 kV → THD 5%, indiv 3%; HV 69–161 kV → THD 2.5%, indiv 1.5%; EHV >161 kV → THD 1.5%, indiv 1%.

FAQ
¿Qué es IEEE 519-2014?
IEEE 519-2014 establece límites de distorsión armónica en tensión y corriente en el punto de acoplamiento común (PCC) entre cliente y red eléctrica.
¿TDD vs THD?
THD expresa harmónicos respecto al fundamental. TDD expresa harmónicos de corriente respecto a la corriente de carga máxima IL. IEEE 519 usa TDD para límites de corriente.
¿Cómo afecta Isc/IL a los límites?
Mayor Isc/IL indica red más rígida con mayor capacidad de absorción armónica. IEEE 519 otorga límites más altos para redes más rígidas.
¿Qué es la regla de armónicos pares?
Según §5.1, los armónicos pares están limitados al 25% de los límites impares correspondientes.
¿Qué clase de tensión aplica?
BT ≤ 1 kV (THD 8%); MT ≤ 69 kV (THD 5%); AT 69–161 kV (THD 2,5%); EAT > 161 kV (THD 1,5%).
¿Cuáles son fuentes armónicas típicas?
VFDs de 6 pulsos producen 5.°, 7.°, 11.°, 13.° armónicos. Accionamientos de 12 pulsos suprimen 5.°/7.°. SAI/servidores generan 3.°, 5.°, 7.°. Inversores VSC producen espectro amplio.