Transformer & feeder voltage drops, tap changer settings, regulation percentage, and feeder voltage profile.
Leave blank to assume ideal ratio
Leave blank to derive from PF
Voltage drop as percentage of base voltage, derived from transformer impedance components and load current at load angle φ. R and X are separated from Z% using the X/R ratio.
On-load tap changers (OLTC) adjust transformer turn ratio in 0.625% or 1.25% steps. Position = required compensation / step size. Typical range: ±16 steps (±10%). Off-load tap changers (ULTC) require de-energisation.
Three-phase voltage drop along a uniform feeder. R and X per km from conductor tables (IEC 60287 for XLPE, IEC 60502 for EPR). Profile shows linear voltage decrease assuming uniform load distribution.