Three-phase initial symmetrical (I"k), peak (ip), breaking (Ib), and steady-state (Ik) short-circuit currents. Grid infeed, transformer, cable, and motor contributions.
c_max = 1.10 for max Ik (IEC Table 1)
Leave pkr blank to derive R_T from ukr% and X/R ratio
The grid infeed impedance Zq represents the source strength. For a local substation with strong grid infeed (high Sk"), Zq is small and the fault level is high.
Transformer impedance is defined by ukr% at rated current. Copper losses pkr (kW) allow accurate split of Z into R and X. Vector group affects zero-sequence network for unbalanced faults.
ip is the first peak of the short-circuit current, important for circuit breaker making capacity. The peak factor κ depends on the R/X ratio at the fault location.
Breakers are rated for symmetric interrupting current (Icw) and peak making current. LV breakers (≤1 kV) typically have a peak-to-symmetric ratio of 2.5. HV breakers use κ factor directly.