FrameAI Examples SCADA & Security Fire Detection — NFPA 72
SCADA & Security · Worked Example

Design the smoke detector spacing for a single-storey warehouse: 30 m × 20 m plan area, 9 m clear height, smooth flat ceiling. The facility is classified Ordinary Hazard Group 1 per NFPA 72 (2019 edition). Determine required detector spacing, coverage area per detector, and minimum detector count.

NFPA 72 (2019) · NFPA 72 (2019) Table 17.6.3.2.1
Input parameters
Room dimensions 30 m × 20 m (600 m²)
Ceiling height h = 9.0 m
Ceiling type Smooth, flat (no obstructions)
Hazard class Ordinary Hazard Group 1
Standard used NFPA 72 (2019)
Ambient temperature 20 °C (ordinary)
Mounting height 9.0 m (ceiling mount)
Run your own version of this calc →
RESULT NFPA 72 (2019)
Governing check Detector spacing (height-corrected)
Result value 8.5 m grid
Utilization
PASS
All checks
Check Status Util. Value
Base spacing — Ordinary Hazard PASS
S_base = 12.1 m (40 ft) centre-to-centre
Height correction (h > 4.3 m) PASS
k_h = 0.9 — 30% reduction, S_adj = 8.5 m
Coverage area per detector PASS
A_det = 72.3 m² ≤ 80 m² max for 9 m height
Minimum detectors required PASS
N = 9 detectors (3 rows × 3 columns, 8.5 m grid)
Spot-type detector spacing PASS
D_max = 9.2 m between detectors
Distance to wall (≤ 0.5 × S) PASS
max 4.25 m from any wall — compliant
standard NFPA 72 (2019) Table 17.6.3.2.1
method Spot-type detector spacing by height
partialFactors Height factor k_h = 0.90 (h = 9.0 m)
Compute time 0.2 s

Run your own version of this calculation

Enter your own input values — or use the same numbers and double-check. The Fire Detection — NFPA 72 tool is free to use, no account required.

Open Fire Detection — NFPA 72 →