Size the three-phase 400 V supply cable for an industrial motor load of 400 A continuous rating, 50 m underground run through a concrete duct bank. The installation is in a thermal resistivity soil of 1.2 K·m/W, ambient temperature 25°C, with 4 circuits in the same duct. Select the minimum XLPE copper conductor cross-section per IEC 60287 and verify voltage drop.

IEC 60287 / HD 60364-5-52 · IEC 60287-1-1 / HD 60364-5-52 Table B.52.1
Input parameters
Load current I_b = 400 A
Conductor material Copper, XLPE insulation
Installation Buried in concrete duct, 4 circuits
Run length L = 50 m
Ambient temperature θ_a = 25 °C
Soil thermal resistivity ρ_s = 1.2 K·m/W
System voltage 400 V, 50 Hz, 3-phase
Power factor cos φ = 0.88
Reactance x = 0.08 Ω/km
Max permitted VD 3% (12 V)
Run your own version of this calc →
RESULT IEC 60287 / HD 60364-5-52
Governing check Ampacity — conductor cross-section
Result value 527 A
Utilization
PASS
All checks
Check Status Util. Value
Ampacity — derating factors PASS
I_r = 507 A (target), cable must carry ≥ 507 A
Conductor selected PASS
3 × 240 mm² XLPE Cu (I_r = 527 A ≥ 507 A)
Voltage drop — IEC 60287 PASS
ΔU = 7.3 V (1.83%) ≤ 12 V (3%)
Earth fault loop impedance PASS
Z_s = 0.082 Ω ≤ 0.167 Ω
Short-circuit thermal withstand PASS
I²t = 4.8 × 10⁶ A²s ≤ 7.2 × 10⁶ A²s limit
Group derating (4 circuits) PASS
k_g = 0.78 — applied to base ampacity
standard IEC 60287-1-1 / HD 60364-5-52 Table B.52.1
method Neher-McGrath (IEC 60287)
partialFactors k_t = 0.87 (ambient), k_g = 0.78 (group)
Compute time 0.5 s